ASSESSMENT OF CURRENT TRANSFORMER USING HEALTHY INDEX AT ULTG PANAKKUKAN

Authors

  • Uais Rizqan Politeknik Negeri Ujung Pandang
  • Sarma Thaha Politeknik Negeri Ujung Pandang

Keywords:

Conditional Assessment Factor, Performance Assessment Factor, Assessment Healthy Index

Abstract

Current transformers (CTs) play a crucial role in the measurement and protection of electrical networks, directly impacting the performance and stability of the distribution system. Over time, the condition of current transformers can degrade due to factors like age, environmental conditions, and overloads. To ensure the health status of these transformers, an assessment method using the Healthy Index (HI) is applied. This research utilizes data from tests on tan delta, insulation resistance, ratio, thermography, excitation, and the age of the current transformer. The data is categorized into two factors: the Conditional Assessment Factor (CAF), which provides a real-time condition overview from tan delta data (where values above 1% indicate poor and values below or equal to 1% indicate good condition), insulation resistance (where values below or equal to 1 Mega Ohm/1kV indicate poor and above 1 Mega Ohm/1kV indicate good), thermography (where temperatures above 4°C are considered poor, temperatures between 1°C and 3°C are medium, and normal temperatures relative to ambient conditions are good), and ratio; and the Performance Assessment Factor (PAF), which assesses equipment performance based on transformer age. Age classifications are 20-35 years as poor, 16-20 years as medium, and below 16 years as good. Following the gathering of CAF and PAF data, a systematic calculation of each factor's weighting is conducted using the Assessment Healthy Index (AHI) Calculation method, resulting in assessment ratings of 1 for poor, 6 for medium, and 9 for good. From these categories, conclusions can be drawn regarding the next steps for the current transformer, determining whether repair or replacement with a new transformer is necessary.

References

[1] AM Abdullah. “Prediction of Transformer Health Index Using Condition Situation Monitoring (CSM) Diagnostic Techniques”, Review 334 (2023), diakses pada 13 Februari 2023, https://iopscience.iop.org/article/ 10.1088/1742-6596/1878/1/012007

[2] AnungPLN, “Komponen-komponen/Peralatan Pada Switchyard Gardu Induk”, (2014), Diakses 26 September 2024, https://scadaku.wordpress.com/ 2014/05/22/komponen-komponen-peralatan-pada-switchyard-gardu-induk/

[3] Atul Jaysing Patil. “A Novel Fuzzy Based Technique For Transformer Health Index Computation”, Review 219 (2020), diakses pada 16 Februari 2024, https://ieeexplore.ieee.org/abstract/document/9036845

[4] Bernadus Wijayaka. “PLN Bangun Gardu Induk Digital di Teluk Naga Tangerang”, (2022), Diakses 26 September 2024, https://www.beritasatu.com/ekonomi/928367/pln-bangun-gardu-induk-digital-di-teluk-naga-tangerang/2

[5] Cecep Munawar. “Pengujian CT Dengan CT Analyzer Omicron”, (2018), diakses 26 September 2024, https://cecepmunawar.wordpress.com/2018 /08/27/pengujian-ct-dengan-ct-analyzer-omicron/

[6] Daniella Gonzalez Tinois Da Silva. “Enhanced health index for power transformers diagnosis”, Review 21 (2020), diakses pada 16 Februari 2024, https://www.sciencedirect.com/science/article/abs/pii/ S1350630721002879

[7] Dimas Jarot Bayu. “Kejar Target 35 Ribu MW, Menteri Airlangga: Butuh Banyak Gardu GIS, (2018), Diakses 26 September 2024, https://katadata.co.id/berita/industri/5e9a55bc9df54/kejar-target-35-ribu-mw-menteri-airlangga-butuh-banyak-gardu-gis

[8] Doni Ramdhani. “PLN Berupaya Normalkan ALiran Listrik di Balongan”, (2021), Diakses 26 September 2024, https://www.inilahkoran.id/pln-berupaya-normalkan-aliran-listrik-di-balongan

[9] “Flir E5 With Thermal Imaging Camera”,(2020), diakses 26 September 2024, https://www.kucari.com/product/flir-e5/

[10] Hong Guo. “Health index for power transformer condition assessment based on operation history and test data”, Review 37 (2022), diakses pada 16 Februari 2024, https://www.sciencedirect.com/science/ article/pii/S2352484722013075

[11] I Gusti Ngurah Satriyadi Hernanda. Application of Health Index Method for Transformer Condition Assesment

[12] Juventri Buntu Payung, 2023. Rancang Bangun Sistem Tracking Dan Pembersih Permukaan Panel Surya Berbasis Mikrokontroler

[13] Karyana, 2013. Sistem Proteksi Transmisi dan Gardu Induk

[14] Manual book FLIR Exx Series 2016

[15] Manual book MIT515 / MIT525 /MIT1025 / MIT15255 kV, 10 kV and 15 kV Insulation Resistance Testers Megger 2022

[16] Manual book CPC 100 Omicron 2005

[17] “Megger MIT525 Insulation Tester”, (2023), Diakses 26 September 2024, https://www.cemandiri.com/product/jual-megger-mit525-insulation-tester/

[18] PT. PLN (Persero). 2009. Materi Workshop Operasi dan Pemeliharaan Gardu Induk

[19] Raji Murugan. ”Understanding the power transformer component failures for health index-based maintenance planning in electric utilities”, Review 127 (2018), diakses pada 16 Februari 2024, https://www.sciencedirect.com/science/article/abs/pii/S1350630718308550

[20] SK.DIR 520 Thn. 2014 PT.PLN (Persero) Kantor Pusat , Buku Pedoman Pemeliharaan Trafo Arus (CT)

[21] “TestGear”(2024), diakses 26 September 2024, https://testgear.co.nz/equipment/cp-td-1/

[22] Wang Jian. “The New Developed Health Index for Power Transformer Condition Assessment”, Review 367 (2020), diakses pada 16 Februari 2024, https://ieeexplore.ieee.org/abstract/document/9136344

[23] Winanda Riga Tamma. “High voltage power transformer condition assessment considering the health index value and its decreasing rate”, Review 19 (2021), diakses pada 16 Februari 2024, https://ietresearch.onlinelibrary.wiley.com/doi/full/ 10.1049/hve2.12074

[24] Zuhal. 1992. Dasar Teknik Tenaga Listrik dan Elektronika Daya., Jakarta: Gramedia Pustaka.

Downloads

Published

2025-05-02

Issue

Section

Articles