ANALISIS PERBANDINGAN PENERAPAN SISTEM GRID-ROD DAN GRID TAK SIMETRI PADA PEMBUMIAN GARDU INDUK

Authors

  • Tadjuddin Tadjuddin
  • Bakhtiar Bakhtiar

Abstract

The grid-rod system has been widely used in grounding substation, while the grid unequally spaced known in the 90s .This reseach aims to determine the mesh voltage of both systems when there is ground fault. In addition to determiningthe length of the required electrode at the same mesh voltage. In this research used secondary data that the soilresistivity 37.5 ohm-m, and the substation has a size 42m x 40m . This data is obtained at the unit induk pembangunanxiii Makassar. Calculations are done by simple regression and the results are analized by quantitative and qualitativemethod. (5)The result of the research concluded that : i). the grid-rod system obtained 455.4 volt mesh voltage and 1232meter electrode length with 6 meter parallel conductor spacing, ii). For the grid unequally spaced obtained mesh voltage463 volt, With a 656 m length electrode. iii). When the unequally spaced grid is used, an electrode saving of 45 % isobtained at the same level security, when using a grid-rod system.

References

. ANSI/IEEE std 80[1986]: An American national Standart, IEEE Guide Safetyin AC Substation grounding.

. Baldev Thapar, Victor Gerez and prince Emmanuel, 1993: Ground Resistance of the foot In Substation Yard,

IEEE Transaction on Delivery, vol.8 No.1pp-1-6

. Baldev Thapar, Victor Gerez and Vijai Singh [1993]: Effective Ground Resistance of the Human Feet In High

Voltage Switchyards “, IEEE Transaction on Power Delivery vol. 8 No.1 pp.7-12.

. F.P Dawalibi, J. Ma, R.D Southey, 1994, Behaviar of Grounding System in Multilayer soil: A parametric Anaysis,

IEEE Transaction on Power Delivery vol. 9 No.1 pp.334-342.

. J.M Nahman V.B Djordjevic, 1995, Non uniformly Correction Factor for maximum mesh and step Voltage of

Grounding Grid and combined Ground electrode, IEEE Transaction on Power Delivery vol. 10 No.3 pp.1263-1269.

. J.M Nahman V.B Djordjevic, 1996, Resistance To Ground of Combined Grid-Multiple Rods Electrodesa,

Transaction on Power Delivery vol. 11 No.3 pp.1337-1342.

. L.Huang, XChen, H. Yan. 1995. Study of Unequally spaced Grounding Grids, Transaction on Power Delivery,

Vol.10 no.2, April 1995, pp716-722

. M.M.A Salama, M.M. Elsherbiny and Y. L Chow, 1995, A Formula for Resistanceof Substation Grounding in Two

Layer Soil, IEEE Transaction on Power Delivery vol. 10 No.3 pp.1255-1262

. PUIL 2011. Persyaratan Umum Instalasi Listrik 2011, Badan Standarisasi Nasional.

.Tadjuddin, 1998, Analisis Pengaruh perubahan Tahanan Jenis Tanah Terhadap Tegangan Permukaan dan

Tahanan Pembumian System Grid-Rod pada Strutur Dua Lapisan Tanah.

. Tadjuddin, 2015. Analisis penerapan Sistem grid Unequally Spaced pada pembumian gardu Induk

. T.S Hutauruk. 1991. Pengetanahan Netral Sistem Tenaga dan Pengetanahan Peralatan, Penerbit Erlangga,

Jakarta.

. Y.L Chow ,M.M. Elsherbiny, M.M.A Salama, 1996, Resistance Formula of Grounding System in Two Layer

Earyh, IEEE Transaction on Power Delivery vol. 11 No.3 pp.1330-1336.

Downloads

Published

2018-08-28

Issue

Section

ELEKTRO, KOMPUTER & JARINGAN, MEKATRONIKA, TELEKOMUNIKASI, DAN INFORMATION COMMUNICATION & TECHNOLOGY